470 AC POWER SYSTEMS


IR

+


+


VS = VS ∠δ VR = VR ∠^0 °

IS Z = jX

Figure P10.3.1Simple model of loss-
less transmission line.

IR
+


+


VS VR

IS

Two-port
network

Sending end Receiving end

Figure P10.3.3

10.3.10On a per-phase basis, letv=



2 Vcosωtand
i=


2 Icos(ωt−θ).

(a) Express the instantaneous powers(t) in terms
of real powerPand reactive powerQ.

(b) Now consider the energyEassociated with
the instantaneous power and show thatE=
Pt, wheretis the duration of the time interval
in seconds.

10.3.11A 60-Hz, three-phase transmission line has a total
per-phase series impedance of 35+j 140 .Ifit
delivers 40 MW at 220 kV and 0.9 power factor
lagging, find:


(a) The voltage, current, and power factor at the
sending end of the line.
(b) The voltage regulation and efficiency of the
line.
10.3.12A three-phase, 60-Hz transmission line has a total
series impedance of 22. 86  62 .3°per phase. It
delivers 2.5 MW at 13.8 kV to a load connected
to its receiving end. Compute the sending-end
voltage, current, real power, and reactive power
for the following conditions:
(a) 0.8 power factor lagging.
(b) Unity power factor.
(c) 0.9 power factor leading.