23.3.3 Potential Transformers
IN
OUT
Ratio correction factor (RCF)¼
true ratio
marked ratio
(RCF generally>1)
Burden is measured in VA ;VA¼
E^2
Assume Zb
10:1
10 V 0.9 Zb
RX
True ratio¼
10
0 : 9
¼ 11 : 1
)RCF¼
11 : 1
10
¼ 1 : 11
Marked ratio¼
10
1
¼ 10
Voltage at secondary is low and must be compensated by 11% to get the actual primary voltage using the
marked ratio.
23.3.4 Current Transformer
True ratio¼marked ratioRCF
;RCF¼
true ratio
marked ratio
23.3.5 H-Class
Vs is fixed
Is varies Nearly constant ratio error in %