23.3 Instrument Transformers
23.3.1 Two Types
- Potential (usually 120 V secondary)
- Current (5 A secondary at rated primary current)
23.3.2 Accuracy
Three factors will influence accuracy:
- Design and construction of transducer
- Circuit conditions (V,I, andf)
- Burden (in general, the higher the burden, the greater the error)
1.0A(a)(b)(c)BC1.0
1.01.01.0
0 00
0
0.8660.866bacbacbac1.01.00.5770.5770.5770.50A B C A B C1.00.500.577
0.5770.577(^00)
0
0.50
0.50
0
FIGURE 23.12 D-Y transformer banks.
TABLE 23.4 Distribution Transformer Overload with Normal Loss of Life
Duration of Peak Load
Self-cooled with % Load before Peak of:
(Hours) 50 70 90
0.5 189 178 164
1 158 149 139
2 137 132 124
4 119 117 113
8 108 107 106