Drawing Number
1.5Single Door - Level 4 - StrikeDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access StandardsCeilingStructure48 in AFFTo Card Access Panel½ in flex raceway w/string.
¾ in conduit raceway w/string.RDRLCKTo Video SystemDevice Rough In RequirementsJBDevice Description Opening
F
UPIR / ALM FS1in conduit sleeve into JB from
unsecured side of door
IPC
CAMSJB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSideRDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
CAM location or exterior lcoation, provide a 4sq box at location with a ¾ in raceway to cable Accessible location near cable tray, no rough-in is required. In a inaccessible ceiling
tray. Coordinate the inaccessible locations with the SSC
C CeilingU6inDSMDSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F FrameLCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F FramePIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.PHUUPH ¾ conduit raceway from un-secured ceiling into the wall down to the PH location. Provide 4sq box in wall with 1G mud ring vertical. Owner furnished phone. Owner Installed Phone U CeilingTypical Application : Designated Exterior Access Doors, Restricted Access DoorsNovember 1, 2016