Architectural and Engineering Design Standards

(avery) #1
Drawing Number
1.12

Double Door - Level 4 - Elec Panics

Date:

UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011

CV

Job Number

Serial Number Drawn By

Project
Documents

Revisions

Drawing Type
Card Access Details

None

Safety & Security Card Access Standards

1in conduit sleeve into JB from
unsecured side of door

Ceiling

Structure

48 in AFF

J
Box

To Card Access Panel

¾ in EMT Raceway with pull string
½ in Flex Raceway with pull string


RDR

PIR / ALM

To Video System

DSM

EP EP

Located on public
side of door

Device Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide

RDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
CAM location or exterior lcoation, provide a 4sq box at location with a ¾ in raceway to cable Accessible location near cable tray, no rough-in is required. In a inaccessible ceiling
tray. Coordinate the inaccessible locations with the SSC
C Ceiling

U
F

F

F

S

S

DSM

U

Door can be Single or Double Egress.
Coordinate with SSC and GC on Device locations

F

EP
Power
Supply

½ in Flex Raceway for EP Only
(Informational Only)

S

IP

U
CAM

DSM Use PIR / ALM raceway to PIR / ALM Box. Provide a pull wire from this box location to each DSM switch. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.

PH

U

U

PH ¾ conduit raceway from un-secured ceiling into the wall down to the PH location. Provide 4sq box in wall with 1G mud ring vertical. Owner furnished phone. Owner Installed Phone U Ceiling

EP ½ flex raceway from power supply to each transfer hinge. This work is shown for coordination of rough ins only. Wiring related to Electrified Panics by EC F Frame

Typical applications : Low Usage Clinic Door (Access Controls)

LCK LCK

F F

LCK ½ flex raceway from PIR into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame

DH alarm is active and door holder circuit is released. Wiring related to DH and EP by EC.Door Holder Circuit is tied to the power supply. EP’s normally retracted unless a fire F Ceiling

DH

PTE
Located on secured
side of door

S

S

PTE ¾ conduit raceway from the ceiling to the PTE location. Provide 4sq box in wall with 1G mud ring vertical. S SecuredSide

Sequence
Door will be monitored and alarmed by Software House system if forced or held
open.
Electrified Panics will be retracted during normal operation. Extended during fire
alarm.
Mag Locks will secure the door under normal operation. Mag Locks de-energized
during fire alarm and EP will extend to latch.

KS

U

KEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide

November 1, 2016