Architectural and Engineering Design Standards

(avery) #1
Drawing Number
1.14

Double Door - Level 3 - Mag Lock

Date:

UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011

CV

Job Number

Serial Number Drawn By

Project
Documents

Revisions

Drawing Type
Card Access Details

None

Safety & Security Card Access Standards

1in conduit sleeve into JB from
unsecured side of door

Ceiling

Structure

48 in AFF

J
Box

To Card Access Panel

¾ in EMT Raceway with pull string
½ in Flex Raceway with pull string

RDR

PIR / ALM

DSM

To Video System

DSM

PTE

LCK

KEY
Located on secured
side of door
Located on public
side of door

Device Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide


RDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide

S U U

F F F F

S

S

KEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
PTE ¾ conduit raceway from the ceiling to the PTE location. Provide 4sq box in wall with 1G mud ring vertical. S SecuredSide

LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame

DSM

S U

Door can be Single or Double Egress.
Coordinate with SSC and GC on Device locations.

DSM Use PIR / ALM raceway to PIR / ALM Box. Provide a pull wire from this box location to each DSM switch. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.

LCK

Note:
1 If door is double egress, the leaf exiting the secured
space does not require a LCK or PTE if no pull hardware
is provided.

Note 1

Note 1

November 1, 2016