Architectural and Engineering Design Standards

(avery) #1
Drawing Number
1.16

Double Door - Level 3D - Institutional

Date:

UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011

CV

Job Number

Serial Number Drawn By

Project
Documents

Revisions

Drawing Type
Card Access Details

None

Safety & Security Card Access Standards

1in conduit sleeve into JB from
unsecured side of door

Ceiling

Structure

J
Box

To Card Access Panel

¾ in EMT Raceway with pull
string
½ in Flex Raceway with
pull string


RDR

To Video System

DSM

KEY
Located on secured
side of door
Located on public
side of door

Device Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide

RDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide

S U U

F F F F

S

KEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide

LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame

DSM

U U

DSM Use LOCK raceway to LOCK Box. Provide a pull wire from this box location to each DSM switch. F Frame

KEYRDR

S

48 in AFF

Typical applications for this door are institutions applications that require card in card out control

LCK LCK

Door can be Single or Double Egress.
Coordinate with SSC and GC on Device locations

November 1, 2016