Drawing Number
1.17Double Door - Level 4D - InstitutionalDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access Standards1in conduit sleeve into JB from
unsecured side of doorCeilingStructure48 in AFFJ
BoxTo Card Access Panel¾ in EMT Raceway with pull
string
½ in Flex Raceway with
pull stringRDRTo Video SystemDSMKEY
Located on secured
side of door
Located on public
side of doorDevice Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSideRDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
CAM location or exterior lcoation, provide a 4sq box at location with a ¾ in raceway to cable Accessible location near cable tray, no rough-in is required. In a inaccessible ceiling
tray. Coordinate the inaccessible locations with the SSC
C CeilingS U UF F F FSUKEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSideLCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F FrameDSMU UDoor can be Single or Double Egress.
Coordinate with SSC and GC on Device locationsIPCAMDSM Use LOCK raceway to LOCK Box. Provide a pull wire from this box location to each DSM switch. F FrameKEYRDRS S USIP
CAMPHPH ¾ conduit raceway from un-secured ceiling into the wall down to the PH location. Provide 4sq box in wall with 1G mud ring vertical. Owner furnished phone. Owner Installed Phone C CeilingTypical applications for this door are institutions applications that require card in card out controlLCK DSM DSM LCKPHNote:
1 Remote release is required at the designated nurses
station to unlock the door.November 1, 2016