Architectural and Engineering Design Standards

(avery) #1
Drawing Number
1.17

Double Door - Level 4D - Institutional

Date:

UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011

CV

Job Number

Serial Number Drawn By

Project
Documents

Revisions

Drawing Type
Card Access Details

None

Safety & Security Card Access Standards

1in conduit sleeve into JB from
unsecured side of door

Ceiling

Structure

48 in AFF

J
Box

To Card Access Panel

¾ in EMT Raceway with pull
string
½ in Flex Raceway with
pull string

RDR

To Video System

DSM

KEY
Located on secured
side of door
Located on public
side of door

Device Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide

RDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
CAM location or exterior lcoation, provide a 4sq box at location with a ¾ in raceway to cable Accessible location near cable tray, no rough-in is required. In a inaccessible ceiling
tray. Coordinate the inaccessible locations with the SSC
C Ceiling

S U U

F F F F

S

U

KEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide

LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame

DSM

U U

Door can be Single or Double Egress.
Coordinate with SSC and GC on Device locations

IP

CAM

DSM Use LOCK raceway to LOCK Box. Provide a pull wire from this box location to each DSM switch. F Frame

KEYRDR

S S U

S

IP


CAM

PH

PH ¾ conduit raceway from un-secured ceiling into the wall down to the PH location. Provide 4sq box in wall with 1G mud ring vertical. Owner furnished phone. Owner Installed Phone C Ceiling

Typical applications for this door are institutions applications that require card in card out control

LCK DSM DSM LCK

PH

Note:
1 Remote release is required at the designated nurses
station to unlock the door.