Drawing Number
1.16
Double Door - Level 3D - Institutional
Date:
UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011
CV
Job Number
Serial Number Drawn By
Project
Documents
Revisions
Drawing Type
Card Access Details
None
Safety & Security Card Access Standards
1in conduit sleeve into JB from
unsecured side of door
Ceiling
Structure
J
Box
To Card Access Panel
¾ in EMT Raceway with pull
string
½ in Flex Raceway with
pull string
RDR
To Video System
DSM
KEY
Located on secured
side of door
Located on public
side of door
Device Rough In Requirements
Device Description Opening
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide
RDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
S U U
F F F F
S
KEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame
DSM
U U
DSM Use LOCK raceway to LOCK Box. Provide a pull wire from this box location to each DSM switch. F Frame
KEYRDR
S
48 in AFF
Typical applications for this door are institutions applications that require card in card out control
LCK LCK
Door can be Single or Double Egress.
Coordinate with SSC and GC on Device locations
November 1, 2016