Hardware Manual

(John Hannent) #1

Saia-Burgess Controls AG


Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Communication interfaces

4


PCD7.F180

4.5.6 MP-Bus with PCD7.F180, Port #1 (without PCD1.M110)


PCD7.F180:
Connecting module for MP-Bus, for socket A
The user has a facility to connect an MP-Bus line with 8 drives
and sensors.

Connections

10
11
12
13
14
15
16
17
18
19 19

18

17

16

14

13

12

11

PCD7.F180

Socket A

A COM
,MST’
,IN’
GND





Screw terminal block, socket A

MP-Bus signal line (18 V in/out)
MST programming unit (MP-Bus internal)
MST programming unit detection (input 10 kΩ, Z5V1)
Earth connection, MST programming unit

GND (Branch A–)


  • GND


Supply option
Common supply for control and drive

·
·

&&

Edgi&

'(%K 6XijVidgh

68
+%L &.K^68

H^)6I

E89&$E89'


BHIegd\gVbb^c\jc^i

&(

&%

&-
&.

&)
&*
&+
&,

"

$9

9

L9
"
"

&'

When using the PCD7.F180 connection module, the supply voltage to the PC control unit
must be at least 24 VDC, ±5 % (not the default tolerance of ±20 %).

With a separate DC or AC supply to the drives, it is especially important to ensure that the
PCD control unit is connected to the earth (Minus pole) of the drive supply. The earth serves
as a common base for communication.
For details, see Technical Information P+P26 / 342
“MP-Bus interface for BELIMO actuating drives”