5.2 Digital input modules, electrically isolated
PCD2.E500 6 inputs for 115 - 230 VAC
PCD2.E610 8 inputs 24 VDC, 10 ms
PCD2.E611 8 inputs 24 VDC, 0.2 ms
PCD2.E613 8 inputs 48 VDC, 9 ms
PCD2.E616 8 inputs 5 VDC, 0.2 ms,Galvanic separation of outputs to PCD.
The channels themselves not are separated.Definition of input signalsfor 24 VVDC for 115 – 230 VVAC(PCD2.E610...E616)PCD2.E610 ... E616)) (PCD2.E500)(PCD2.E500)(PCD2.E500)PCD2.E500))30V
24V
15V0V5V-30V1
0
1
0
250 VAC80 VAC
40 VAC
0 VACInstallation instructionsFor reasons of safety it is not permissible to connect low voltages (up to 50 V) and
higher voltages (50 ... 250 V) to the same module.If a PCD module is connected to a higher voltage (50 ... 250 V), approved compo-
nents for this voltage must be used for all elements that are electrically connected to
the system.Using higher voltage (50 ... 250 V), all connections to the relay contacts must be
connected on the same circuit, i.e. in such a way that they are all protected against
one AC phase by one common fuse. Each load circuit may also be protected
individually.I/O modules and I/O terminal blocks may only be plugged in and removed when the PCD is