Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


Expansion housings and bus cables

CPUs and expansion housings

3


3.6.2 Expansion with PCD3 components


For local expansion, the PCD3 LIO (Local I/O) modules can be used:
PCD3.C200 4 plug-in I/O modules, integrated 24 VDC / 5 VDC supply for
modules and signal refresh.
PCD3.C100 4 plug-in I/O modules
PCD3.C110 2 plug-in I/O modules

(^) Frontview
(^) Frontview
0 16 32 48
112 96 80 64
128 144 160 176 192 208 224 240 ...1023
Bus extension cable
PCD2.M1xx and M4xx
PCD3.C100/200
Frontview Frontview
For decentralized expansion, the PCD3 RIO (Remote I/O) modules can be used:
PCD3.T760 Integrated Profibus DP Slave / Profi S-Net Slave connection up to
max. 1.5 MBit/s
4 plug-in I/O cassettes
Integrated web server for diagnostics, support and comissioning
(Connection to PC via optional PCD3.K225 connector cable)tional PCD3.K225 connector cable)
The maximum number of I/Os is dependent on the controller being used:
PCD type Maximum number
PCD3 I/Os
Maximum number
I/Os per system
PCD2.M120/150 127 255
PCD2.M170 382 510
PCD2.M480 897 1023
PCD3.RIO nodes 256 per node Determined by the maximum
size of the I/O process map
for DP Master