Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
Power supply and connection plan
CPUs and expansion housings
3
3.9 Power supply and connection plan
3.9.1 External power supply
Simple, small installations
+18V
0V
LN GND
19VAC
±15%
Transformer min. 50VA
Sensors: Electro-mechanical switches
Actuators: Relays, lamps, small valves with < 0.5 A switching current
The transformer voltage of 19 VAC ±15% must be maintained. If not, the supply voltage at
the input to the PCD may become too high and destroy it.
The PCD2. H1xx, H2xx, H3xx, PCD7.D1xx, D2xx and PCA2.D12/D14 modules must be
connected to a smoothed 24 VDC supply
Small to medium installations
+24V =
0V
GND
L
N ±20%
LN
CONTROLLER 24 VDC
Controller: usual primary switched network component
Sensors: Electro-mechanical and proximity switches, photoelectric
barriers
Actuators: Relays, lamps, displays, small valves with < 0.5 A switching
current