Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces4
Serial interface on Port #14.4.4 RS 485 communication interface PORT #1, only on PCD1.M110RS 485 communication interface PORT #1, only on PCD1.M110 communication interface PORT #1, only on PCD1.M110communication interface PORT # 1, only on PCD1.M110
On the PCD1.M110, on Port #1, is a built-in RS 485 interface.PCD1.M110, on Port #1, is a built-in RS 485 interface., on Port #1, is a built-in RS 485 interface.10
11
12
1312
13
14
15
16
17
18
19OPENCLOSED191817161411PGND
RX - TX
/RX - /TXPGND
RX - TX
/RX - /TXGNDBus RS 485not usedBus-cableScrew-
terminal-
block APCD1.M 110 Bus RS 485Choice of the termination resistors+ 5 VPCD 1 .M 110
Port #1PCD 1 .M1xx
PCD2.Mxx0PCD 1 .M1xx
PCD2.Mxx0PCD 1 .M1xx
PCD2.Mxx0/RX-/TXn n11 n/n/n /n12RX-TX+ 5 V
Pullup
330 OhmTermination
Resistor
150 OhmSegment length max. 1200 m
max. 32 stationsBusRS 485First station Middle stations End stationPulldown
330 OhmAt the first and last stations, the jumper must be set to the “CLOSED“ position.
At all other stations, the jumper must be set to “OPEN” (factory setting).