Hardware Manual

(John Hannent) #1

Saia-Burgess Controls AG


Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Communication interfaces

4


Serial interface on Port#0

4.4.3 PGU connection (PORT # 0, only on PCD2.M1x0) (RS 485) as communica-
tion interface


If Port #0 is not used via the PGU connection (with the programming device or as
an RS 232 interface), it can be used via terminals 28 and 29 for an S-Bus or MC4
connection.


29

27
26
25
24
23
22
21
20

D
/D

WD
WD

J 0

OP

EN
CL

OS

ED

PCD 2 .M 110
PCD2.M120
PCD2.M150

RX - TX
/RX - /TX 28

RS 485
Bus-cable

Screw terminal block

29

27
26
25
24
23
22
21
20

D
/D

WD
WD

J 0
OPEN

CLOSED

PCD2.M170

28

Choice of line termination resistors

+ 5 V

/RX-/TX

n n

29 n

/n

/n /n

28

RX-TX

PCD 2 .M1x0
Port #0

PCD 1 .M1xx
PCD2.Mxx0

PCD 1 .M1xx
PCD2.Mxx0

PCD 1 .M1xx
PCD2.Mxx0
+ 5 V
Pullup
330 Ohm
Termination
Resistor
150 Ohm

Segment length max. 1200 m
max. 32 stations

BusRS 485

First station Middle stations End station

Pulldown
330 Ohm

At the first and last stations, jumper J0 must be set to the “CLOSED“ position.
At all other stations, jumper J0 must be set to “OPEN” (factory setting).