48 HANDBOOK OF ELECTRICAL ENGINEERING
Similarly for generators Nos. 2 and 3,
fz 2 = 61 .6Hzandfz 3 = 61 .5Hz
Step 2. The common system frequency after the load increases is found from (2.66), (2.67) and (2.68).
a=
1
60. 0
(
60. 9 × 20. 0
0. 03
+
61. 6 × 15. 0
0. 04
+
61. 5 × 10. 0
0. 05
)
= 1266. 67
b=
1
60
(
20. 0
0. 03
+
15. 0
0. 04
+
10. 0
0. 05
)
= 20. 6945
f=
a−P
b
=
1266. 67 − 40. 5
20. 6945
=59.25101 Hz
Step 3. Find the new load on each generator
P 1 =(fz 1 −f)
G 1
D 1 fo
=( 60. 9 − 59. 25101 )
20. 0
0. 03 × 60. 0
=18.3221 MW (91.61%)
Similarly for generators Nos. 2 and 3,
P 2 =14.6819 MW (97.88%) andP 3 =7.4966 MW (74.97%)
Note,
Pnew=P 1 +P 2 +P 3 = 18. 3221 + 14. 6819 + 7. 4966
=40.5 MW as required.
Step 4. Find the new set points that will recover the frequency to 60 Hz.
If a changePiinPiis added to the (2.69) then the change in the set point will be,
fzi=
DiPifo
GI
(or 60. 0 −f)
For generator No. 1,
fz 1 =
0. 03 ×( 18. 3221 − 10. 0 ) 60. 0
20
= 0. 74899
And so the new set-point isfz 1 +fz 1 = 61 .6489 Hz
Similarly for generators Nos. 2 and 3
fz 2 +fz 2 =62.3491 Hz, andfz 3 +fz 3 =62.2489 Hz
Step 5. Find the set points that will enable the generators to be equally loaded.