GAS TURBINE DRIVEN GENERATORS 49
For generator No. 1, the ratioK 1 of its new load to its rating is,
P 1 +P 1
G 1
=K 1
Similarly for generators Nos. 2 and 3,
P 2 +P 2
G 2
=K 2 and
P 3 +P 3
G 3
=K 3
For the generators to be equally loadedK 1 =K 2 =K 3 =K.
In addition the ratio of the total load to the total of the generator ratings must be the same as
for each generator,
Hence,
K=
P 1 +P 1 +P 2 +P 2 +P 3 +P 3
G 1 +G 2 +G 3
K=
40. 5
20 + 15 + 10
= 0. 9
Therefore since
P 1 +P 1
G 1
= 0. 9
P 1 =( 0. 9 × 20 )− 10. 0 =8.00 MW
so that
P 1 +P 1 =18.00 MW (90%)
and
P 2 =( 0. 9 × 15 )− 10. 0 =3.5 MW
so that
P 2 +P 2 = 10. 0 + 3. 5 =13.5 MW (90%)
and
P 3 =( 0. 9 × 10 )− 5. 0 =4.0 MW
so that
P 3 +P 3 = 5. 0 + 4. 0 =9.0 MW (90%)
Step 6. Find the new set points.
From (2.62), for generator No. 1, using the original frequency of 59.25101 Hz, found in Step 2,
fz 1 = 59. 25101 +
0. 03 × 18. 00 × 60. 0
20. 0
=60.871 Hz