Electric Power Generation, Transmission, and Distribution

(Tina Meador) #1
23.1.6 Calculation of Fault Current
Line Faults
Line-to-neutral fault¼

E
ffiffiffi
3

p
2 Z‘
whereZ‘is the line impedance and 2Z‘is the loop impedance assuming the impedance of the phase
conductor and the neutral conductor are equal (some people use a 1.5 factor).
Line-to-line fault¼E= 2 Z‘
Transformer Faults
Line-to-neutral or three-phase¼
E
ffiffiffi
3

p
ZT
Line-to-line¼
E
2(ZTþZ‘)

whereZ‘¼

ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
RL^2 þXL^2

p

ZT¼
ZT% 10 E^2
kVA

23.1.7 Current Limiting Fuses
Current limiting fuses (CLFs) use a fusible element (usually silver) surrounded by sand (Fig. 23.7).
When the element melts, it causes the sand to turn into fulgerite (glass). Since glass is a good insulator,

600

500

400

300

200

100

0
012
Time (minutes)

345

% of Normal Peak CurrentRelay
Pickup

15-Minute Outage

10-Minute Outage

5-Minute Outage

FIGURE 23.6 Cold load inrush current characteristics for distribution circuits.

FIGURE 23.7 Full range current limiting fuse. (Courtesy T&B. With permission.)

Free download pdf