Electric Power Generation, Transmission, and Distribution

(Tina Meador) #1

23.3.3 Potential Transformers


IN

OUT

Ratio correction factor (RCF)¼
true ratio
marked ratio

(RCF generally>1)

Burden is measured in VA ;VA¼
E^2

Assume Zb


10:1

10 V 0.9 Zb

RX

True ratio¼
10
0 : 9

¼ 11 : 1

)RCF¼

11 : 1
10
¼ 1 : 11

Marked ratio¼

10
1
¼ 10

Voltage at secondary is low and must be compensated by 11% to get the actual primary voltage using the
marked ratio.


23.3.4 Current Transformer


True ratio¼marked ratioRCF

;RCF¼
true ratio
marked ratio

23.3.5 H-Class


Vs is fixed
Is varies Nearly constant ratio error in %