Drawing Number
1.21Pharmacy Single Door - Level P1Date:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access StandardsCeilingStructure48 in AFFTo Card Access Panel½ in flex raceway w/string.
¾ in conduit raceway w/string.6inDSMDevice Rough In RequirementsJBDevice Description Opening
PIR / ALM FS1in conduit sleeve into JB from
unsecured side of door
SJB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSideUDSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.Typical Application : Pharmacy Department Door MonitoringKEYKEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSideSequence
Door will be monitored and alarmed by Software House system if forced or held
open.
Key switch will provide user arm disarm function of door to shunt alarm during
occupied hours. Red Light indicates “armed” green light indicates “disarmed”November 1, 2016