Drawing Number
1.22
Pharmacy Single Door - Level P3 - Prox Reader
Date:
UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011
CV
Job Number
Serial Number Drawn By
Project
Documents
Revisions
Drawing Type
Card Access Details
None
Safety & Security Card Access Standards
Ceiling
Structure
48 in AFF
To Card Access Panel
½ in flex raceway w/string.
¾ in conduit raceway w/string.
6in
RDR
LCK
DSM
Device Rough In Requirements
JB
Device Description Opening
F
U
PIR / ALM F
S
1in conduit sleeve into JB from
unsecured side of door
S
JB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSide
RDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
U
DSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F Frame
LCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F Frame
PIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.
Typical Application : Pharmacy Department Access Door (Non Pharmacy Areas)
KEY
KEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSide
U
Sequence
Door will be monitored and alarmed by Software House system if forced or held
open.
Key switch will provide user arm disarm function of door to shunt alarm during
occupied hours. Red Light indicates “armed” green light indicates “disarmed”
Card Reader function will be disabled if the key switch is armed.
November 1, 2016