Drawing Number
1.23Pharmacy Single Door - Level P3 - Biometrics ReaderDate:UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011CVJob NumberSerial Number Drawn ByProject
DocumentsRevisionsDrawing Type
Card Access DetailsNoneSafety & Security Card Access StandardsCeilingStructure48 in AFFTo Card Access Panel½ in flex raceway w/string.
¾ in conduit raceway w/string.6inRDRLCKDSMDevice Rough In RequirementsJBDevice Description Opening
F
UPIR / ALM FS1in conduit sleeve into JB from
unsecured side of door
SJB 4sq Junction Box on secure side of door. ¾ in sleeve to unsecured side of door. Cables will be routed from the cable pathway in the corridor thru this sleeve into the JB. S SecuredSideRDR ¾ conduit raceway from un-secured ceiling into the wall down to the RDR location. Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSideUDSM ½ flex raceway from J-Box into the wall down to a ¾ in opening in frame. 6 in from end of door. Coordinate the location on frame and drilling with the GC. F FrameLCK ½ flex raceway from J-Box into the wall down to the door lock location. Coordinate the location on frame with the GC. F FramePIR
ALM
Secured
S Side
½ flex raceway from secured side of room into the wall down to the PIR/ALM location.
Provide 4sq box in wall with 1G mud ring horizontal.KEYKEY ¾ conduit raceway from the RDR to the KS.Provide 4sq box in wall with 1G mud ring vertical. U UnSecuredSideUSequence
Door will be monitored and alarmed by Software House system if forced or held
open.
Key switch will provide user arm disarm function of door to shunt alarm during
occupied hours. Red Light indicates “armed” green light indicates “disarmed”
Card Reader function will be disabled if the key switch is armed.Typical Application : Pharmacy Department Access Door (Pharmacy Areas)November 1, 2016