TABLE 7.2 Examples of Nominal Size versus Actual Size of Some Engineering Products
Dimension of Copper Tubing (Type K— for high pressure – temperature use)

Nominal Outside Inside Wall Flow Cross
Size (in.) Diameter (in.) Diameter (in.) Thickness (in.) Section (in

2


)


1/4 0.375 0.305 0.035 0.073
3/8 0.5 0.402 0.049 0.127
1/2 0.625 0.527 0.049 0.218
5/8 0.75 0.652 0.049 0.334
3/4 0.875 0.745 0.065 0.436
1 1.125 0.995 0.065 0.778
1 1.375 1.245 0.065 1.22
1 1.625 1.481 0.072 1.72
2 2.125 1.959 0.083 3.01
2 2.625 2.435 0.095 4.66
3 3.125 2.907 0.109 6.64
3 3.625 3.385 0.120 9.00
4 4.125 3.857 0.134 11.7
5 5.125 4.805 0.160 18.1

1


2


1


2


1


2


1


4


Dimension of Copper Tubing (Type L — for HVAC applications)


Nominal Outside Inside Wall Flow Cross
Size (in.) Diameter (in.) Diameter (in.) Thickness (in.) Section (in^2 )

1/4 0.375 0.315 0.030 0.078
3/8 0.5 0.44 0.035 0.145
1/2 0.625 0.545 0.040 0.233
5/8 0.75 0.666 0.042 0.334
3/4 0.875 0.785 0.045 0.484
1 1.125 1.025 0.065 0.825
1 1.375 1.265 0.050 1.26
1 1.625 1.505 0.055 1.78
2 2.125 1.985 0.060 3.09
2 2.625 2.465 0.070 4.77
3 3.125 2.945 0.080 6.81
3 3.625 3.425 0.090 9.21
4 4.125 3.905 0.100 11.0
5 5.125 4.875 0.110 18.1

1


2


1


2


1


2


1


4


Continued


7.3 Nominal Sizes versus Actual Sizes 169