PCD2.E160/161Input/output (I/O) modules5
Input circuits and terminal designation
Depending on external wiring, this module may be used for source or sink operation.
Source operation (positive logic):17,1,19,3,5,21,^723 25,9,11,27,13,29,^1531
L E1E030 3210 k 10 k10 k 10 kUe 24 VDCRibbon cable connectorSwitch closed: (+ at input): signal state "H", LED lights up
Schalter open: signal state "L", LED offLED redLED green
If both inputs 0 and 1 are
switched on, the yellow (orange)
LED lights upSink operation (negative logic):17, 19, 21, 23^1 , 3, 5, 7 25, 27, 29, 319, 11, 13, 15
L E1 E030 32Ue 24 VDCRibbon cable connectorSwitch closed: (- at input): signal state "L", LED off
Switch open: signal state "H", LED lights upWatchdog: This module can interact with the watchdog; if it is used on base address
240 (or 496 for the PCD2.M17x), the last input with address 255 (or 511 for the
PCD2.M17x) cannot be used.
For details, please refer to the “Watchdog” section, which describes the correct use of
the watchdog in conjunction with PCD2 components.