Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W11x
Input/output (I/O) modules
5
Technical data for add-on modules (variant modules)
PCD2.W110 4 inputs for Pt 100 probes
Current sources 2 mA
Measuring range -50 °C ... +150 °C
Accuracy of measurement better than 0.2 °C
PCD2.W111 4 inputs for Ni 100 probes
Current sources 2 mA
Measuring range -50 °C ... +150 °C
Accuracy of measurement better than 0.4 °C
PCD2.W112 4 inputs for Pt 1000 probes
Current sources 0.2 mA
Measuring range -50 °C ... +150 °C
Accuracy of measurement better than 0.2 °C
PCD2.W113 4 inputs for Ni 1000 probes
Current sources 0.2 mA
Measuring range - -50 °C ... +150 °C
Accuracy of measurement better than 0.4 °C
PCD2.W114 4 inputs for Pt 100 probes
Current sources 0.2 mA
Measuring range 0 °C ... +350 °C
Accuracy of measurement better than 0.4 °C
Accuracy of measurements
The curves below show the maximum measurement error
(measurement and repeating accuracy).
Total error = linearization error + repeating error
Each channel is calibrated to the minimum and maximum values:
-50 °C → 0 + 2 LSB
+150 °C → 4095 - 2 LSB
For these two values, the measurement error = 0.