Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W11x
Input/output (I/O) modules
5
Typical linearity error for W110/112/114 (Pt 100/Pt 1000)
- 50
0
0
1024
+ 50
2047. 5
+ 100
3071
+ 150
4095 °LCSB
Measurement
Deviation (LSB)
0
+ 1
+ 2
+ 3
+ 4
+ 5
+ 1
+ 2
+ 3
+ 4
+ 5
+ 6
+ 6
Typical linearity error for W111/113 (Ni 100/Ni 1000)
- 50
0
0
1024
+ 50
2047. 5
+ 100
3071
+ 150
4095 °LCSB
Measurement
Deviation (LSB)
0
+ 1
+ 2
+ 3
+ 4
+ 5
+ 1
+ 2
+ 3
+ 4
+ 5
+ 6
+ 6
On cable break → Measurement 4095
On short circuit → Measurement 0
Base and variant modules
Each module comprises 2 individual modules.
● Base module with input filters, A/D converter, I/O port. Same module with same
fittings for all 4 variants.
● Plug-on variant modules with switching circuit to generate -15 V, power sources
and linearization. Each of the four variants has a module of its own, i.e. a
module with different equipment.
The user has access to the 4 potentiometers to set the offset for each individual
channel. This can be useful for adjusting the zero value (at -50 °C) for long
measurement cables.
All modules are set up in pairs (base and variant module) at the factory. The variant
modules must not be exchanged.