Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W3x0
Input/output (I/O) modules
5
Digital/analogue values
Input signals and type Digital values
PCD2.W300/W340 PCD2.W310/W340 PCD2.W340/50/60 Classic xx7 Simatic
+ 10.0 V + 20 mA Calculate the appro-
priate values with the
formulae at the end
of this section
4095 4095 27684
+ 5.0 V + 10 mA 2047 2047 13824
0 V 0 mA 0 0 0
Connection concept for voltage and current inputs
The voltage and current input signals are connected directly to the 10-pole terminal
block (E0 ... E7). To minimize the amount of interference coupled into the module
via the transmission lines, connection should be made according to the principle
explained below.
The following connection diagram shows a typical wiring layout for:
● voltage inputs with the PCD2.W300 and ... W340 Modules or
● current inputs with the PCD2.W310 and ... W340 Modules
9 8
E6
7 6
E4
5 4
E1
3 2
E0
1 0
E7 E5 E3 E2
Earthing bar
max. 20cm
COM
Distributor *)
*) potential free
● The reference potentials of signal sources should be wired to a common GND
connection (“–” and “COM” terminals). To obtain optimum measurement results,
any connection to an earthing bar should be avoided
● If shielded cables are used, the shield should be continued to an external earthing
bar.