Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W3x0
Input/output (I/O) modules
5
Connection concept for temperature sensors
The input signals for the temperature sensors are connected directly to the 10-pole
terminal block (E0 ... E7).
The following connection diagram shows a typical layout for tempera-
ture sensors with the PCD2.W340, ... W350 and ... W360 Modules.
9 8
E6
7 6
E4
5 4
E1
3 2
E0
1 0
E7 E5 E3 E2
Earthing bar
max. 20 cm
COM
Distributor *)
*) potential free
● The reference potential for temperature measurements is the “COM” terminal,
which should not have any external earth or GND connection.
● If screened cables are used, screening should be continued to an external
earthing bar.
● Unused temperature inputs are to be connected to the logical ground.
Mixed operation
9 8
E6
7 6
E4
5 4
E1
3 2
E0
1 0
COM E7 E5 E3 E2
Distributor
V and C
Distributor
Temp.