Saia-Burgess Controls AG
Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Communication interfaces
4
Serial interface on Port #1
4.4.4 RS 485 communication interface PORT #1, only on PCD1.M110RS 485 communication interface PORT #1, only on PCD1.M110 communication interface PORT #1, only on PCD1.M110communication interface PORT # 1, only on PCD1.M110
On the PCD1.M110, on Port #1, is a built-in RS 485 interface.PCD1.M110, on Port #1, is a built-in RS 485 interface., on Port #1, is a built-in RS 485 interface.
10
11
12
13
12
13
14
15
16
17
18
19
OPEN
CLOSED
19
18
17
16
14
11
PGND
RX - TX
/RX - /TX
PGND
RX - TX
/RX - /TX
GND
Bus RS 485
not used
Bus-cable
Screw-
terminal-
block A
PCD1.M 110 Bus RS 485
Choice of the termination resistors
+ 5 V
PCD 1 .M 110
Port #1
PCD 1 .M1xx
PCD2.Mxx0
PCD 1 .M1xx
PCD2.Mxx0
PCD 1 .M1xx
PCD2.Mxx0
/RX-/TX
n n
11 n
/n
/n /n
12
RX-TX
+ 5 V
Pullup
330 Ohm
Termination
Resistor
150 Ohm
Segment length max. 1200 m
max. 32 stations
BusRS 485
First station Middle stations End station
Pulldown
330 Ohm
At the first and last stations, the jumper must be set to the “CLOSED“ position.