Architectural and Engineering Design Standards

(avery) #1
Drawing Number
1.20

Software House iStar 2 Reader Edge Panel Layout

Date:

UI Hospitals & Clinics
Iowa City Iowa 52242
Scale
4/27/2011

CV

Job Number

Serial Number Drawn By

Project
Documents

Revisions

Drawing Type
Card Access Details

None

Safety & Security Card Access Standards

PS-1

Power
Supply

Max 36 inches

AFF 78 inches

By Others (Electrical Contractor),
120Vac Emergency Power, Dedicated Circuit(s)


By Others (Network provider),Network IP Connection DropNet F.A.

Device Description

Fire
Alarm

Fire Alarm contractor to provide a NC contact at the panel for the SSC contractor to
connect to the lock power supplies to drop in event of a fire alarm. This will provide Magnetic Lock interuption.

Network
Drop Provide Network wire run for connection to panel. 10/100 connection on SecNet

120V
EmergencyPower Provide 120 VAC Emergency Power dedicated to this equipment

By Others (Fire Alarm System),
Mag Lock Interuption Connection

Notes:
1 Fire Alarm contractor to test mag lock power interuption
during testing