Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22
Saia-Burgess Controls AG
PCD2.W3x0
Input/output (I/O) modules
5
Time constant of input filter: W300: typically 10.5 ms
W310: typically 12.4 ms
W340 V: typically 7.8 ms
C: typically 24.2 ms
T: typically 24.2 ms
W350: typically 16.9 ms
W360: typically 16.9 ms
Internal current consumption:
(from +5 V bus)from +5 V bus)
< 8 mA for all module typesfor all module types
Internalcurrent consumption:
(from V+ bus)
W300, 310 < 5 mA
W340, 360 < 20 mA
W350 < 30 mA
External current consumption: 0 mA
Terminals: Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
*) No negative input voltage should be applied on these modules.
Terminals
9 8 7 6 5 4 3 2 1 0
+E 7 +E 6 +E 5 +E 4 +E 3 +E 2 +E 1 +E 0
E 7 E 6 E 5 E 4 E 3 E 2 E 1 E 0
T
V/ 4
V
C
T
V/ 4
V
C
T
V/ 4
V
C
T
V/ 4
V
C
T
V/ 4
V
C
Bus connector
Bus interface
A/D converter and
Voltage reference
Amplifier (OP-AMP)
Jumper für working
Mode selection
(PCD2.W340 only)
Input filter
Screw terminals
COM
T
V/ 4
V
C
T
V/ 4
V
C
T
V/ 4
V
C
T
V/ 4
V
C
Position'T': Pt/Ni 1000
Position'V/ 4 ':( 0 ..+ 2. 5 V)
Position'V': 0 ..+ 10 V
Position'C': 0 .. 20 mA
Jumper positions for selecting working mode
PCD2.W340 only; on the other module types the working modes are fixed
All inputs set for temperature (position T) must be wired. All unused inputs (with the
W340) must be adjusted to current range ‘C’ or voltage range ‘V’.
Changing the jumpers
On this circuit board there are components that are sensitive to electrostatic
discharges. For further information, refer to Appendix B, “Icons”.