Hardware Manual

(John Hannent) #1

Hardware Manual PCD 1 / PCD 2 Series│Document 26 / 737│Edition EN 15│2008-07-22


Saia-Burgess Controls AG


PCD2.W3x0

Input/output (I/O) modules

5


Connection concept for two-wire transducers

E1

E0

GND

PCD 2 .W 310 /340


0 ...20 mA

4 ...20 mA*

R






2 4 VDC

Pressure

Tempera-
ture

Input filter


+

E2

*4...20 mA over user program

Two-wire transducers need a 24 VDC-supply in the measuring trunk.
Block diagram

E0
E1
E2
E3
E4
E5
E6
E7

GND


Rsource


Voltage
Source
10.000V

Ref.
Voltage
2.500V

Input filterand amplifier


MUX


A


D


Data


I/O Bus
PCD Bus

+5V
GND

/IOOUIT
IODIN
/IOWRITE
IODOUT
I/MS0
IOA0
IOA1
IOA2
IOA3

W340, W350, W360 only


Programming
Classic: Programming examples for the PCD2.W3x0 can be found in a separate
manual and on the TCS Support site (www.sbc-support.ch + getting started).
xx7: the firmware reads in the values according to the configuration (I/O Builder)
Watchdog: This module cannot be used on the base address 240 (or 496 for the
PCD2.M17x), because it would interact with the watchdog, and would cause a
malfunction.
For details, please refer to the “Watchdog” section, which describes the correct use of
the watchdog in conjunction with PCD2 components.