Communication interfaces
4
Serial interface on Port#0
PCD8.K110 connection cable (obsolete)
(P8 protocol, suitable for PCD1.M110 / 120 and PCD2.M110 / 120 only)
SGN SGN
TX
RX
RTS
CTS CTS
RTS
TX
2 RX
1
4
3
6
5
8
7
D-SUB pol.
(female)
D-SUB 9 pol.
(male)
9
2
1
4
3
6
5
8
7
9
PC DSR PLC
4.4.2 PGU connection (PORT # 0, PCD1 and PCD2) (RS 232) as communication
interface
When comissioning / programming are complete, the port can be used for other pur-
poses.
Option 1: Configuration with desired protocol
(S-Bus PGU configuration)
Option 2: Assignment (SASI) in the user program
(the port must not be configured as an S-Bus PGU port)
■ If another programming device is connected during operation
instead of the peripheral device, the unit will switch over
automatically to PGU mode (pin 6 logical “1” (DSR); in PGU
mode: DSR PING = “1”).
■ Before using the port to connect another peripheral device,
Port #0 must be reconfigured by means of an SASI instruction.
GND SGN
TX
RX
RTS 1)
CTS CTS 1)
RTS
TXD
2 RXD
1
4
3
6
5
8
7
PGU-Plug
D-SUB 9 pol.
(female)
Peripheral
9
DCD
Cable
PGD
1) When communicating with terminals, check whether some connections are pro-
vided with bridges or need to be set to “H” or “L” with the “SOCL” instruction. It is
generally recommended to use a handshake (RTS / CTS)