Architectural and Engineering Design Standards
Appendix G UIHC Pneumatic Tube System (Section 14 92 00) November 1, 2016 ...
SECTION 14 92 00 November 1, 2016 HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-1 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLINI ...
SECTION 14 92 00 November 1, 2016^ HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-2 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLIN ...
SECTION 14 92 00 November 1, 2016 HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-3 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLINI ...
SECTION 14 92 00 November 1, 2016 HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-4 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLINI ...
SECTION 14 92 00 November 1, 2016 HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-5 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLINI ...
SECTION 14 92 00 November 1, 2016 HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-6 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLINI ...
SECTION 14 92 00 November 1, 2016 HOSPITAL WIDE PNEUMATIC TUBE SYSTEM 149200-7 UIHC # THE UNIVERSITY OF IOWA HOSPITALS AND CLINI ...
Appendix H UI Emergency Generator Specifications November 1, 2016 ...
APPENDIX H University of Iowa Emergency Generator Specifications The intent of these specifications is to establish a level of q ...
Engine Room Temperature: 120° F Detailed capacity requirements shall be as set forth in paragraph 5. Diesel Engine – Generato ...
Cooling shall be provided by a remotely installed radiator unit of the vertical discharge style. d. Lubrication System A pressur ...
As an alternate to the Base Bid, the vendor shall provide a hydraulic governing system in lieu of the electronic type. The vendo ...
7) Low battery voltage. 8) High battery voltage. 9) Low fuel supply. As an alternate to the Base Bid, the vendor shall provide m ...
o. Battery Charger A battery charger shall be furnished. The charger shall employ a transistor controlled magnetic amplifier cir ...
b) Ammeter Selector Switch, 4 position, to measure current flow in all phases. c) Voltmeter – 2% of full scale accuracy. d) Volt ...
(2) Fan Cycle Off. 3) Switchgear: a) Main Circuit Breaker: (1) 1600 ampere, 480 volt, 3 phase. (2) Molded Case Type – U.L. liste ...
(3) Space ventilation equipment starters. j) Audible alarm with silencing switch to alarm when any one or more of the immediate ...
r. Remote Radiator A remote radiator, of the quiet type, shall be provided as follows: 1) Welded and bolted steel frame suitable ...
Torsional Analysis It shall be certified that a mathematical torsional analysis has been made of a like combination of engine ...
«