Architectural and Engineering Design Standards
Rev. 13 November 1, 2016 Page | 41 Toilet Seat Cover Dispenser: Silhouette Toilet Seat Cover Dispenser, Model #19510, col or: B ...
Rev. 13 November 1, 2016 Page | 4.11 Division 11 – Equipment for Roof Standards Update 11 24 23 Window Washing Systems Tie-off ...
Rev. 13 November 1, 2016 Page | 43 4.13 Division 13 – Special Construction 13 49 00 Radiation Protection Design shall be submit ...
Rev. 13 November 1, 2016 Page | 44 4.15 Division 21 – Fire Suppression 21 05 00 Common Work Results for Fire Suppression During ...
Rev. 13 November 1, 2016 Page | 45 b. Provide each standpipe take-off with a 2-1/2” x 1-1/2” cap on a chain. Fire Pump Controll ...
Rev. 13 November 1, 2016 Page | 46 21 13 00 Fire Suppression Sprinkler Systems 21 13 13 Wet-Pipe Automatic Sprinkler Systems Th ...
Rev. 13 November 1, 2016 Page | 47 4.16 Division 22 – Plumbing 22 05 00 Common Work Results for Plumbing For both new construct ...
Rev. 13 November 1, 2016 Page | 48 a. Install horizontal sections o f domestic water m ains above-ceiling in corridors. b. Pipi ...
Rev. 13 November 1, 2016 Page | 49 c. Install all water ha mmer arrestors in an upright position. Valves a. All valves 3” diame ...
Rev. 13 November 1, 2016 Page | 50 a. For typical sanitary waste and vent systems of 3” diameter and above, install service weig ...
Rev. 13 November 1, 2016 Page | 51 22 14 13 Storm Sewer Piping Systems Materials a. For typical storm sewer systems of 3” diame ...
Rev. 13 November 1, 2016 Page | 52 Watts (four bolt model only) 22 14 26.16 Areaway Drainage Review with Owner the specific t ...
Rev. 13 November 1, 2016 Page | 53 For typical vitreous china and cast iron plumbing fixtures, all units shall be by Kohler, Zu ...
Rev. 13 November 1, 2016 Page | 54 Medical Gas Outlets a. Coordinate the type of medical gas outlet required at each location. ...
Rev. 13 November 1, 2016 Page | 55 d. All medical air compressors shall be of the liquid-cooled rotary screw type with internal ...
Rev. 13 November 1, 2016 Page | 56 Figure 1: Typical drawing of reserve cylinder room. Figure 2: Existing reserve cylinder room ...
Rev. 13 November 1, 2016 Page | 57 Oxygen Distribution a. The Design Professional shall determine the adequacy of capacity of a ...
Rev. 13 November 1, 2016 Page | 58 23 05 53 Identification for HVAC Piping and Equipment Provide equipment identification on al ...
Rev. 13 November 1, 2016 Page | 59 b. The Testing and Balancing Contractor (TBC) shall have a minimum of five years’ experience ...
Rev. 13 November 1, 2016 Page | 60 A single pressure gauge connected directly at the suction and discharge ou tlets of the pump ...
«