Rev. 13 November 1, 2016 Page | 61 i. All 24 volt wiring shall be installed by the TCC. This wiring shall be installed either in ...
Rev. 13 November 1, 2016 Page | 62 Design Phase Coordination a. The Design Professional shall, during the design phase, coordin ...
Rev. 13 November 1, 2016 Page | 63 c. Install horizontal sections of mechanical piping mains above-ceiling in corridors unless a ...
Rev. 13 November 1, 2016 Page | 64 ii. The main building distribution system shall include points for supply temperature (one pe ...
Rev. 13 November 1, 2016 Page | 65 Other a. Install manual air vents at accessible locations i. At the top of all risers. ii. A ...
Rev. 13 November 1, 2016 Page | 66 Cooling C oil Condensate Pipi ng S ystems Materials a. Install Type L ASTM B88 copper with w ...
Rev. 13 November 1, 2016 Page | 67 d. For interior steam and condensate piping with pressures below 75 ps ig, and 2 inch diamete ...
Rev. 13 November 1, 2016 Page | 68 23 30 00 HVAC Air Distribution Isolation Rooms a. Label the exhaust air duct from isolation ...
Rev. 13 November 1, 2016 Page | 69 a. Fire dampers shall be Style B construction with the damper blades out of the air stream un ...
Rev. 13 November 1, 2016 Page | 70 b. Specify extra capacity on all components within the air ha nd ling unit to pr ovide future ...
Rev. 13 November 1, 2016 Page | 71 Final Filter Sections a. All fi lte r racks shall be gasketed. b. Fina l filters shall be 95 ...
Rev. 13 November 1, 2016 Page | 72 23 83 16 Radiant Heating Radiant ceiling panel systems shall be designed for heating only. I ...
Rev. 13 November 1, 2016 Page | 73 a. All wire and cable for power, lighting, control and signal circuits shall have copper cond ...
Rev. 13 November 1, 2016 Page | 74 stripe) shall be installed in the panel feeder and all branch ci rcuits. A green grounding co ...
Rev. 13 November 1, 2016 Page | 75 ii. Flexible Metal Conduit: Use for final connections to dry type transformer, connections fr ...
Rev. 13 November 1, 2016 Page | 76 i. In Stud Walls: For single or double outlet, use 4 inch square by 1-1/2 inch deep box. Boxe ...
Rev. 13 November 1, 2016 Page | 77 b. The University of Iowa Facilities Management Electrical Distribution Department will provi ...
Rev. 13 November 1, 2016 Page | 78 c. Disconnect switches used with motor-driven appliances, and motors and controllers shall be ...
Rev. 13 November 1, 2016 Page | 79 b. The basis of design shall be Square D. Lighting and Appliance Panelboards a. Lighting and ...
Rev. 13 November 1, 2016 Page | 80 26 27 00 Electrical Distribution Equipment General: a. Manufacturer for all of the electrica ...
«