Architectural and Engineering Design Standards
Rev. 13 November 1, 2016 Page | 21 iii. All .dwgs files shall have all x-refs bound and all raster attachments included. Entitie ...
Rev. 13 November 1, 2016 Page | 22 Construction-Phase Process Installing C ontractor prepa res roofing and roof related sheet m ...
Rev. 13 November 1, 2016 Page | 23 3. DRAWINGS & SPECIFICATIONS 3.1 UIHC Room Numbering The Department of Engi ne ering Serv ...
Rev. 13 November 1, 2016 Page | 24 4. ARCHITECTURAL & ENGINEERING STANDARDS 4.1 Division 01 – General Requirements.......... ...
Rev. 13 November 1, 2016 Page | 25 4.2 Division 02 – Existing Conditions 02 42 00 Selective Demolition Demolition of Lead Shiel ...
Rev. 13 November 1, 2016 Page | 26 4.3 Division 03– Concrete Lightweight structural concrete shall not be specified for roof dec ...
Rev. 13 November 1, 2016 Page | 27 4.4 Division 04 - Masonry Consider roof system thicknesses when designing elevation of transi ...
Rev. 13 November 1, 2016 Page | 28 Plywood shall be used for base flashings substrates at perimeter walls in lieu of gypsum shea ...
Rev. 13 November 1, 2016 Page | 29 07 21 29 Spray Foam Insulation Product to meet Flame Spread and Smoke Developed Rating: ASTM ...
Rev. 13 November 1, 2016 Page | 30 maintain the vapor retarder above the dew point temperature and prevent condensation. Vapor r ...
Rev. 13 November 1, 2016 Page | 31 Non-reinforced black EPDM to be used. Membrane thickness shall be 60 or 90-mils as appropriat ...
Rev. 13 November 1, 2016 Page | 32 All parapet walls, expansion/control joint curbs, and curb-to-ductwork flashings shall be wat ...
Rev. 13 November 1, 2016 Page | 33 a) Where firestop systems not listed by any listing agency are required due to project condit ...
Rev. 13 November 1, 2016 Page | 34 Interior: SDI-100 Grade II, 18ga. faces, seamless edges with 20ga. stiffeners and sound insu ...
Rev. 13 November 1, 2016 Page | 35 f) Windows, factory glazing, thermal barrier and related materials shall have a 10 year gua r ...
Rev. 13 November 1, 2016 Page | 36 Handicapped, barrier-free door controls – Horton 4100 Series. Keying: Final shall be Medeco ...
Rev. 13 November 1, 2016 Page | 37 Insulating glass 1” thick composed of ¼” reflective, heat strengthened bronze tint float gla ...
Rev. 13 November 1, 2016 Page | 38 Carpet to be 100% solution dyed nylon. 6’ wide Tandus Powerbond or approved equivalent. 09 ...
Rev. 13 November 1, 2016 Page | 39 4.10 Division 10 – Specialties 10 14 00 Signage The preferred plaque for LEED accredited fac ...
Rev. 13 November 1, 2016 Page | 40 b) Grab bars – B6806 Series; 1 ½” diameter which conform with ADA regulations. c) Towel bar – ...
«